3 Core N2XSEYFGbY Cu/XLPE/CWS/SFA/PVC MV Cable
- According to DIN VDE 0276, IEC 60502
- Approved by ISO,CCC, CE
- Place of Origin: Henan, China
- Number of Cores: 3
- HS Code: 8544492100
- MOQ: 500 Meters
16~145 $ / Meter
5
- Product Details
N2XSEYFGbY cable is a multi-purpose three-core medium voltage cable. Its excellent resistance to environmental factors meets the different requirements of modern industrial and infrastructure applications. The cables are available in rated voltages from 3.6/6 kV to 18/30 kV to meet the needs of different power systems.
Product Features
- Low dielectric loss
- Water-blocking layer designed to resist water and moisture
- Multi-core structure
- Double armor protection
Application
Whether for power distribution networks in industrial plants, data centers for critical data transmission or outdoor installations, N2XSEYFGbY cables can handle it. It can withstand potential mechanical damage and is designed for installation in the open air, underground, underwater, cable ducts and power stations.
- Specification
- Maximum Conductor Temperature: under normal(90℃), emergency(130℃)
- Permissible short circuit temperature at the conductor: +250°C (Short circuit duration max. 5 s)
- Minimum bending radius: 15x
- Construction
- Class 2 stranded copper conductor
- Inner semi-conductive layer
- XLPE insulation
- Outer semi-conductive layer
- Semi- conductive tape
- Copper wire screen
- Filler
- PVC Separation sheath
- Galvanized flat steel wire
- Galvanized steel tape
- PVC outer sheath (red or black)
- Parameter
| Number of cores and nominal cross section(mm²) |
Overall diameter appr. (mm) |
Cable weight appr.(kg/km) | Conductor DC Resistance at 20℃ (ohm/km) | Current Carrying Capacity at 30°C |
|
| N2XSEYFGbY-3.6/6 KV | In Air | In Ground | |||
| 3×35 | 50.0 | 4355 | 0.5240 | 172 | 154 |
| 3×50 | 53.0 | 5095 | 0.3870 | 205 | 181 |
| 3×70 | 57.5 | 6045 | 0.2680 | 253 | 220 |
| 3×95 | 61.5 | 7165 | 0.1930 | 307 | 263 |
| 3×120 | 65.0 | 8105 | 0.1530 | 352 | 298 |
| 3×150 | 68.0 | 9645 | 0.1240 | 397 | 332 |
| 3×185 | 72.0 | 11055 | 0.0991 | 453 | 374 |
| 3×240 | 77.0 | 13165 | 0.0754 | 529 | 431 |
| 3×300 | 84.5 | 15700 | 0.0601 | 599 | 482 |
| N2XSEYFGbY-6/10 KV | |||||
| 3×35 | 54.5 | 4860 | 0.5240 | 172 | 154 |
| 3×50 | 58.0 | 5650 | 0.3870 | 205 | 181 |
| 3×70 | 62.5 | 6670 | 0.2680 | 253 | 220 |
| 3×95 | 66.0 | 7795 | 0.1930 | 307 | 263 |
| 3×120 | 69.5 | 8765 | 0.1530 | 352 | 298 |
| 3×150 | 73.0 | 10330 | 0.1240 | 397 | 332 |
| 3×185 | 76.5 | 11775 | 0.0991 | 453 | 374 |
| 3×240 | 81.5 | 13855 | 0.0754 | 529 | 431 |
| 3×300 | 88.0 | 16295 | 0.0601 | 599 | 482 |
| N2XSEYFGbY-8.7/15 KV | |||||
| 3×35 | 60.5 | 5570 | 0.5240 | 172 | 154 |
| 3×50 | 63.5 | 6365 | 0.3870 | 205 | 181 |
| 3×70 | 67.5 | 7395 | 0.2680 | 253 | 220 |
| 3×95 | 71.5 | 8555 | 0.1930 | 307 | 263 |
| 3×120 | 75.0 | 9600 | 0.1530 | 352 | 298 |
| 3×150 | 78.5 | 11195 | 0.1240 | 397 | 332 |
| 3×185 | 82.0 | 12680 | 0.0991 | 453 | 374 |
| 3×240 | 87.0 | 14815 | 0.0754 | 529 | 431 |
| 3×300 | 93.5 | 17320 | 0.0601 | 599 | 482 |
| N2XSEYFGbY-12/20 KV | |||||
| 3×35 | 65.5 | 6215 | 0.5240 | 172 | 154 |
| 3×50 | 68.5 | 7070 | 0.3870 | 205 | 181 |
| 3×70 | 73 | 8145 | 0.2680 | 253 | 220 |
| 3×95 | 76.5 | 9310 | 0.1930 | 307 | 263 |
| 3×120 | 80 | 10385 | 0.1530 | 352 | 298 |
| 3×150 | 83.5 | 12050 | 0.1240 | 397 | 332 |
| 3×185 | 87 | 13525 | 0.0991 | 453 | 374 |
| 3×240 | 92 | 15700 | 0.0754 | 529 | 431 |
| 3×300 | 98.5 | 18220 | 0.0601 | 599 | 482 |
FAQ
Where is N2XSEYFGbY cable commonly used?
It is widely used in power distribution networks, industrial plants, substations, and direct burial applications where mechanical stress is expected.
What is the specific advantage of "FGb" (Flat Wire Armor) over standard SWA?
The "FGb" armour consisting of flat galvanized steel wires held by a counter-helix tape provides superior impact resistance and crush protection compared to standard round Steel Wire Armor (SWA). It also allows for a slightly smaller overall diameter compared to heavy-duty round wires of equivalent protection levels, making it ideal for heavy industrial applications.
Is the N2XSEYFGbY cable water-blocked?
The standard "Y" (PVC) version is not longitudinally water-blocked. It relies on the sheath integrity. For wet environments where water migration inside the cable is a concern (e.g., high water table areas), you should specify N2XSEYF(F)GbY (with swellable powder/tapes) or similar longitudinal watertight variants.