0.6/1kv XGB Cable

  • According to IEC and GB Standard
  • Approved by ISO,CE, SGS
  • Place of Origin: Henan, China
  • Number of Cores: multi-core
  • HS Code: 8544492100
6 $ / Meter

5

XGB cable is a 1kV halogen-free power cable with copper conductor, XLPE insulation, and LSZH sheath. It is used for indoor and outdoor power supply in buildings, industrial sites, and public facilities where low smoke, low corrosive gas emission, and flame retardant performance are required. Cable XGB can be installed in ducts, on walls, in vertical shafts, and underground with mechanical protection.

  • Related Voltage: 0.6/1KV
  • Test voltage: 4 KV
  • Bending radius (min): single-core – 15D;  multicore – 12D
  • Operating temperature: -15°C to 60°C
  • Max. conductor temperature: 90°C
  • Max. short-circuit temperature: 250°C
xgb

1. Conductor : copper

2. Insulation : XLPE(cross-linked polyethylene) rated at 90 °C

3 . Inner sheath : LSZH

4. Outer sheath: LSZH

Nominal Cross-Section (mm²) Conductor Shape Max. Resistance at 20°C (Ω/km) Current Capacity in Air (A) Current Capacity in Earth (A) Outer Diam. Min (mm) Outer Diam. Max (mm) Metal Weight (kg/km) Cable Weight (Approx.) (kg/km)
4×1,5 RE 12,1 23 30 8,5 21,1 57,6 205
4×2,5 RE 7,41 32 40 9,5 13,1 96,0 264
4×4 RE 4,61 42 50 10,5 14,6 153,6 349
4×6 RE 3,08 54 65 12,0 16,0 230,4 455
4×10 RE 1,830 75 90 14,0 18,4 384,0 664
4×16 RM 1,150 100 120 17,0 21,0 614,4 953
4×25 RM 0,727 127 150 20,5 25,6 960,0 1439
4×35 RM 0,524 157 175 24,5 29,0 1344,0 1925
4×50 SM 0,387 192 205 26,0 34,0 1920,0 2241
4×70 SM 0,268 246 250 29,0 28,9 2688,0 3088
4×95 SM 0,193 299 305 33,5 43,2 3648,0 4119
4×120 SM 0,153 346 345 37,0 47,8 4608,0 5185
4×150 SM 0,124 399 390 41,0 53,4 5760,0 6460
4×185 SM 0,0991 456 440 46,0 59,3 7104,0 7974
4×240 SM 0,0754 538 510 53,0 67,6 6216,0 10272
4×300 SM 0,524 620 580 59,0 68,7 11520,0 12761

FAQ

Yes. XGB cable is a halogen-free power cable because it uses an LSZH sheath. In fire conditions, it releases less corrosive gas than PVC-sheathed cable.
Yes, but only in protected outdoor installations. XGB cable can be used outdoors in ducts or protected routes where mechanical damage and long-term exposure are controlled.
Yes. XGB cable is UV resistant according to EN 50289-4-17 method A, 720 hours. That makes it suitable for protected outdoor use, but installation design should still consider mechanical protection and route exposure.