HSLH Control Cable
- According to IEC and VDE Standard
- Approved by ISO, CE, SGS
- Place of Origin: Henan, China
- HS Code: 8544492100
- Packing: 100 Meters
- MOQ: 500 Meters
5
- Product Details
The HSLH cable is a halogen-free flexible control cable designed for use in environments where fire safety and the protection of human life and sensitive equipment are critical priorities. The HSLH Cables are composed of halogen-free materials. This construction ensures that in the event of a fire, the cable does not emit toxic corrosive gases or dense black smoke. It is rated for 300/500 V applications and is extensively used in public buildings, industrial machinery, and instrumentation systems. Recommended for medium mechanical stresses in static or continuous motion applications without tensile stresses. Suitable for dry, wet or humid environment. Not recommended for high mechanical stresses and outdoor use.
- Manufactured in alignment with DIN VDE 0295, IEC 60228
- Excellent pliability for easy routing
- Good resistance to greases, coolants, and laboratory chemicals
- Enhanced safety in case of fire: low smoke (EN 61034-2), halogen-free (EN 60754-1, EN 60754-2), flame-retardant (EN 60332-1-2), Corrosivity of Gases (IEC 60754-2 (No Acidity))
- Specification
- Voltage Rating: 300/500 V
- Test Voltage: 4000 V
- Max. Conductor Temperature: 70°C
- Max. Short-Circuit Temperature: 150°C (max. 5 sec)
- Temperature Range: -40°C to +80°C (Fixed); -5°C to +70°C (Moving)
- Min. Bending Radius: 4 x Overall Diameter (Fixed); 15 x Overall Diameter (Moving)
- Construction
- Conductor material: Class 5 Flexible Stranded Copper
- Insulation: LSZH (Low Smoke Zero Halogen)
- Outer Sheath: LSZH (Low Smoke Zero Halogen), Grey
Core Identification:
| JZ | : Black cores with white numbering + yellow – green |
| OZ | : Black cores with white numbering |
| JB | : Coloured cores according to VDE 0293 + yellow – green |
| OB | : Coloured cores according to VDE 0293 |
- Parameter
| Nominal Cross-Section(n×mm2) | Max. Conductor Resistance(at 20°C, Ω/km) | Approx. OverallDiameter (mm) | Copper Index(kg/km) | Approx. Cable Weight(kg/km) |
| 2 x 0.5 | 39.0 | 4.8 | 9.6 | 36 |
| 3 G 0.5 | 39.0 | 5.1 | 14.4 | 43 |
| 4 G 0.5 | 39.0 | 5.7 | 19.2 | 52 |
| 5 G 0.5 | 39.0 | 6.2 | 24.0 | 66 |
| 7 G 0.5 | 39.0 | 6.8 | 33.6 | 82 |
| 12 G 0.5 | 39.0 | 9.0 | 58.0 | 136 |
| 2 x 0.75 | 26.0 | 5.4 | 14.4 | 45 |
| 3 G 0.75 | 26.0 | 5.7 | 21.6 | 56 |
| 4 G 0.75 | 26.0 | 6.2 | 29.0 | 68 |
| 5 G 0.75 | 26.0 | 6.9 | 36.0 | 85 |
| 7 G 0.75 | 26.0 | 7.5 | 50.0 | 110 |
| 12 G 0.75 | 26.0 | 10.0 | 86.0 | 180 |
| 18 G 0.75 | 26.0 | 12.0 | 130.0 | 262 |
| 25 G 0.75 | 26.0 | 14.3 | 180.0 | 360 |
| 2 x 1.0 | 19.5 | 5.8 | 19.2 | 56 |
| 3 G 1.0 | 19.5 | 6.1 | 29.0 | 69 |
| 4 G 1.0 | 19.5 | 6.6 | 38.0 | 84 |
| 5 G 1.0 | 19.5 | 7.3 | 48.0 | 104 |
| 7 G 1.0 | 19.5 | 8.1 | 67.0 | 135 |
| 12 G 1.0 | 19.5 | 10.7 | 115.0 | 225 |
| 18 G 1.0 | 19.5 | 12.8 | 173.0 | 328 |
| 2 x 1.5 | 13.3 | 6.4 | 29.0 | 74 |
| 3 G 1.5 | 13.3 | 6.8 | 43.0 | 90 |
| 4 G 1.5 | 13.3 | 7.4 | 58.0 | 115 |
| 5 G 1.5 | 13.3 | 8.3 | 72.0 | 142 |
| 7 G 1.5 | 13.3 | 9.2 | 101.0 | 185 |
| 12 G 1.5 | 13.3 | 12.2 | 173.0 | 310 |
| 18 G 1.5 | 13.3 | 14.5 | 259.0 | 450 |
| 25 G 1.5 | 13.3 | 17.1 | 360.0 | 635 |
| 3 G 2.5 | 7.98 | 8.3 | 72.0 | 145 |
| 4 G 2.5 | 7.98 | 9.2 | 96.0 | 185 |
| 5 G 2.5 | 7.98 | 10.1 | 120.0 | 230 |
| 7 G 2.5 | 7.98 | 11.2 | 168.0 | 305 |
| 12 G 2.5 | 7.98 | 14.9 | 288.0 | 520 |
| 4 G 4.0 | 4.95 | 10.9 | 154.0 | 285 |
| 5 G 4.0 | 4.95 | 12.3 | 192.0 | 350 |
| 4 G 6.0 | 3.30 | 13.2 | 230.0 | 415 |
| 5 G 6.0 | 3.30 | 14.7 | 288.0 | 505 |
| 4 G 10.0 | 1.91 | 16.5 | 384.0 | 685 |
| 5 G 10.0 | 1.91 | 18.3 | 480.0 | 850 |
| 4 G 16.0 | 1.21 | 19.8 | 614.0 | 1,050 |
| 4 G 25.0 | 0.780 | 24.2 | 960.0 | 1,580 |
| 4 G 35.0 | 0.554 | 27.5 | 1,344.0 | 2,150 |
FAQ
What is the difference between HSLH and YSLY cable?
The main difference is the material. YSLY is PVC-based, while HSLH is Halogen-Free. Choose HSLH for public buildings (hospitals, airports) and data centers. In a fire, it limits smoke and prevents the release of corrosive toxic gases.
Can HSLH cable be used outdoors?
Generally, no. Standard HSLH is engineered for indoor fixed installations. Its halogen-free jacket is typically not UV or weather-resistant. If used outdoors, it must be installed inside protective conduit to prevent degradation from sunlight and moisture.
Is HSLH cable shielded against interference?
No, standard HSLH is unshielded. For applications requiring Electromagnetic Interference (EMI) protection—such as variable frequency drives (VFDs)—you must specify HSLCH. It features a tinned copper braid shield to ensure signal integrity.
Related Products